ER26-1479-001 · 2026-07-20 · Exelon Corporation, The FirstEnergy Transmission Companies

Exelon Corporation and FirstEnergy Service Company submit Request for Rehearing of the 06/18/2026 Order

Text extracted from the eLibrary original (SHA-256 d5fec07de81e3c82…). Download the original from the official source.

Contents · 15 sections
  1. I. Statement of Issues/Specification of Error. p. 3
  2. II. The Burden Under FPA Section 206 Has Not Been Met: The Existing Rate p. 11
  3. A. There is No Evidence In The Record That Loads Served by BTMG Are p. 11
  4. B. The Commission Did Not Engage in Reasoned Decision Making Because It p. 16
  5. C. The Loads Rely Upon The Entire Embedded Transmission System To Serve p. 23
  6. III. The Burden Has Not Been Met Under FPA Section 206: FERC’S Replacement p. 24
  7. A. Allowing Special Treatment For Load Served by BTMG Violates The FPA’s p. 25
  8. B. The Commission’s Emphasis On Protective Systems Is In Tension With The p. 27
  9. C. The June 18, 2026 Order is Arbitrary And Capricious To the Extent it Adopts p. 29
  10. D. The Commission Is Wrong In Suggesting That CD Service Will Promote p. 34
  11. E. The Commission’s Disregard of Reliability Considerations Underscores That p. 36
  12. IV. FERC Exceeded Its Jurisdiction. p. 38
  13. A. FERC’s Replacement Rate Violates the Major Questions Doctrine. p. 38
  14. B. The Commission’s New Approach Infringes On State Retail Authority. p. 39
  15. V. Conclusion p. 42

Read topic-matched comments in ER26-1479

Topics in the text: Filing procedure · Connecting load and generation · Cost allocation

Source sections

Printed headings where available; page ranges otherwise. Excerpts below are selected from the text by keyword.

Opening text

opening text · Topic match: Filing procedure

ER26-1479-000 REQUEST FOR REHEARING OF EXELON CORPORATION AND FIRSTENERGY SERVICE COMPANY Pursuant to Federal Power Act (“FPA”) section 3131 and Rule 7132 of the Rules of Practice and Procedure of the Federal Energy Regulatory Commission (“FERC” or “Commission”), Exelon Corporation3 and FirstEnergy…
Read this passage Filed comments: Filing procedure

I. Statement of Issues/Specification of Error.

printed heading · Topic match: Connecting load and generation

Cir. 2010) (“[T]he Commission ‘must be able to demonstrate that it has made a reasoned decision based upon substantial evidence in the record.’”) (citation omitted); Consol.
Read this passage Filed comments: Connecting load and generation

II. The Burden Under FPA Section 206 Has Not Been Met: The Existing Rate

printed heading

The FPA requires that the rates and charges of a public utility “in connection with the transmission or sale of electric energy subject to the jurisdiction of the Commission, and all rules and regulations affecting or pertaining to such rates or charges shall be just and reasonable.”8 “[A]ny such…
Read this passage

A. There is No Evidence In The Record That Loads Served by BTMG Are

printed heading · Topic match: Connecting load and generation

The Commission states that, it continues to be just and reasonable for an Eligible Customer taking transmission service on behalf of Co-Located Load to elect, as one of the required transmission services from which the Eligible Customer must choose, to take NITS. . . .
Read this passage Filed comments: Connecting load and generation

B. The Commission Did Not Engage in Reasoned Decision Making Because It

printed heading · Topic match: Filing procedure

As an initial matter, picking and choosing customers to receive preferential rate treatment runs contrary to the FPA’s requirement that “[n]o public utility shall, with respect to any 26 See Fla.
Read this passage Filed comments: Filing procedure

C. The Loads Rely Upon The Entire Embedded Transmission System To Serve

printed heading

The Loads Rely Upon The Entire Embedded Transmission System To Serve Their Full Gross Load.
Read this passage

III. The Burden Has Not Been Met Under FPA Section 206: FERC’S Replacement

printed heading

All., 860 F.3d at 663 (“If the Commission finds that a rate is ‘unjust, unreasonable, unduly discriminatory or preferential, the Commission shall determine the just and reasonable rate … and shall fix the same by order,’” and “[i]t is the Commission’s job—not the petitioner’s—to find a just…
Read this passage

A. Allowing Special Treatment For Load Served by BTMG Violates The FPA’s

printed heading

Interconnecting to the grid burdens the system by adding new loads and operating contingencies that must be addressed by system operators.
Read this passage

B. The Commission’s Emphasis On Protective Systems Is In Tension With The

printed heading

Cir. 2014) (per curiam)) (“The cost-causation principle requires that ‘[t]he cost of transmission facilities . . . be allocated to those within the transmission planning region that benefit from those facilities in a manner that is at least roughly commensurate with estimated benefits.’”). 56 See…
Read this passage

C. The June 18, 2026 Order is Arbitrary And Capricious To the Extent it Adopts

printed heading · Topic match: Connecting load and generation

The only exception is when the transmission system requires upgrades to accommodate requests by generators (not load) to interconnect.
Read this passage Filed comments: Connecting load and generation

D. The Commission Is Wrong In Suggesting That CD Service Will Promote

printed heading · Topic match: Reliability and curtailment

Grid operators must plan for such eventualities to ensure system reliability.72 The Commission finds in the December 18, 2025 Order that the BTMG “rules in PJM’s Tariff are no longer just and reasonable because loads with BTMG are not fully accounted for in resource adequacy planning and shift…
Read this passage Filed comments: Reliability and curtailment

E. The Commission’s Disregard of Reliability Considerations Underscores That

printed heading · Topic match: Reliability and curtailment

The Commission’s decision to direct Interim Service be offered to load served by BTMG until all Network Upgrades necessary to provide the requested Network Service are completed overlooks potential resource adequacy risks.
Read this passage Filed comments: Reliability and curtailment

IV. FERC Exceeded Its Jurisdiction.

printed heading

IV.
Read this passage

A. FERC’s Replacement Rate Violates the Major Questions Doctrine.

printed heading

FERC’s Replacement Rate Violates the Major Questions Doctrine.
Read this passage

B. The Commission’s New Approach Infringes On State Retail Authority.

printed heading · Topic match: Retail and wholesale authority

The Commission does not have authority under the FPA to dictate the terms of retail service in that fashion.
Read this passage Filed comments: Retail and wholesale authority

V. Conclusion

printed heading · Topic match: Filing procedure

Conclusion Because neither the Commission nor any other complainant have satisfied their burden under FPA section 206 and the Commission has not engaged in reasoned decision making in the June 18, 2026 Order, the Commission should grant rehearing, revoke its directives June 18, 2026 Order to…
Read this passage Filed comments: Filing procedure

CERTIFICATE OF SERVICE

printed heading

Dated at Chicago, IL this 20th day of July, 2026. /s/ Geneva Kennedy Geneva Kennedy Exelon Corporation
Read this passage