Comments of Verrus LLC in Support of Midcontinent Independent System Operator, Inc.'s proposed Interconnection Reliability Requirements for Large Loads
Text extracted from the eLibrary original (SHA-256 816a9da2c772e8ec…). Download the original from the official source.
Contents · 11 sections
- I. BACKGROUND AND SUMMARY OF POSITION
- II. COMMENTS
- A. MISO’s Risk-Scaled Framework Reasonably Targets Requirements at the Loads That
- B. Verrus Supports Establishing Core Obligations in the Tariff While Reserving
- C. Advanced Computational Loads Are Capable of Actively Supporting Grid Reliability
- D. FERC Action on MISO’s Reliability Requirements Should Be Harmonized with the
- E. MISO’s
- III. CONCLUSION
- Attachment A: Talukdar et al., Mitigating Data Center Impact on Grid Stability: A Coordinated
- Background
- Conclusion
Read topic-matched comments in ER26-3650
Topics in the text: Filing procedure
Source sections
Printed headings where available; page ranges otherwise. Excerpts below are selected from the text by keyword.
Opening text
opening text
ER26-3650-000 for Large Loads ) COMMENTS OF VERRUS, LLC IN SUPPORT OF MISO'S INTERCONNECTION RELIABILITY REQUIREMENTS FOR LARGE LOADS Pursuant to Rule 213 of the Commission’s Rules of Practice and Procedure1, Verrus LLC2 ("Verrus") respectfully submits these comments in support of the…Read this passage
I. BACKGROUND AND SUMMARY OF POSITION
printed heading · Topic match: Filing procedure
As explained below, Verrus (A) supports MISO’s risk-scaled approach to applicability; (B) supports MISO’s choice to establish core obligations in the Tariff, while reserving implementation detail to the Business Practices Manual (“BPM”) and its ongoing stakeholder process; (C) offers its own…Read this passage
II. COMMENTS
printed heading
II.Read this passage
A. MISO’s Risk-Scaled Framework Reasonably Targets Requirements at the Loads That
printed heading
MISO’s Risk-Scaled Framework Reasonably Targets Requirements at the Loads That Present Reliability Risk Verrus supports MISO’s determination to apply the full suite of PMU, ramp, and ride-through requirements only to the Computational Load subset of Large Load, while applying visibility…Read this passage
B. Verrus Supports Establishing Core Obligations in the Tariff While Reserving
printed heading
B.Read this passage
C. Advanced Computational Loads Are Capable of Actively Supporting Grid Reliability
printed heading
Advanced Computational Loads Are Capable of Actively Supporting Grid Reliability Verrus’ own facility design illustrates that computational loads that would be subject to MISO’s proposed requirements are not merely able to comply with them, but can affirmatively support system reliability.Read this passage
D. FERC Action on MISO’s Reliability Requirements Should Be Harmonized with the
printed heading
D.Read this passage
E. MISO’s
printed heading
E.Read this passage
III. CONCLUSION
printed heading
CONCLUSION For the foregoing reasons, Verrus respectfully requests that the Commission accept MISO’s filing in Docket No.Read this passage
Attachment A: Talukdar et al., Mitigating Data Center Impact on Grid Stability: A Coordinated
printed heading
Attachment A: Talukdar et al., Mitigating Data Center Impact on Grid Stability: A Coordinated Control Strategy Using Verrus™ StabiliGrid™ Architecture (Feb. 2026) [to be appended]. 15Transmittal Letter at 30 (requesting an effective date of December 4, 2026). 5 The National Laboratory of the…Read this passage
Table of Contents
printed heading
List of Figures Figure 1.Read this passage
Background
printed heading
This “near miss” has become a primary case study for North American Electric Reliability Corporation and Institute of Electrical and Electronics Engineers (IEEE) working groups, driving new regulatory frameworks that treat data centers not just as passive customers, but as large, dynamic loads that…Read this passage
Conclusion
printed heading
Conclusion Through this coordinated strategy implemented in Verrus StabiliGrid, the data center achieves fault ride-through and rapid recovery for both undervoltage and overvoltage conditions without triggering protection lockouts.Read this passage