EL25-49-000 · 2025-04-23 · Constellation Energy Generation, LLC

Exhibit 4 (Herling)

Text extracted from the eLibrary original (SHA-256 00da0b435184c0d1…). Download the original from the official source.

Contents · 4 sections
  1. I. QUALIFICATIONS AND PURPOSE OF AFFIDAVIT p. 3
  2. II. DESCRIPTION OF CO-LOCATION PROJECT OPTIONS p. 5
  3. III. PROTECTIVE RELAY SCHEMES p. 8
  4. IV. GRID SERVICES p. 10

Read the parent filing

Read topic-matched comments in EL25-49

Topics in the text: Connecting load and generation · Cost allocation · Reliability and curtailment

Source sections

Printed headings where available; page ranges otherwise. Excerpts below are selected from the text by keyword.

Opening text

opening text

EXHIBIT 4 AFFIDAVIT OF STEVEN HERLING UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION PJM Interconnection, L.L.C., et al.
Read this passage

I. QUALIFICATIONS AND PURPOSE OF AFFIDAVIT

printed heading · Topic match: Connecting load and generation

While at PJM, I contributed to or led initiatives that resulted in a wide range of milestone achievements in PJM’s evolution and growth as a regional transmission organization (“RTO”), including the creation of the RTEP process, the development of procedures and standard terms and conditions for…
Read this passage Filed comments: Connecting load and generation

II. DESCRIPTION OF CO-LOCATION PROJECT OPTIONS

printed heading · Topic match: Connecting load and generation

Instead, fully redundant relaying will trip the co-located load in the event of (i) the unplanned loss of the co-located generation or (ii) a reduction in generation level, thereby preventing the co-located load from being able to draw energy from the grid.
Read this passage Filed comments: Connecting load and generation

III. PROTECTIVE RELAY SCHEMES

printed heading · Topic match: Connecting load and generation

Such a configuration uses electric current transformers to measure the flow of power from between the co-located load and the grid, which is communicated with relays via fiber optic channels that will trip behind-the-meter circuit breakers associated with the co-located load when the electric…
Read this passage Filed comments: Connecting load and generation

IV. GRID SERVICES

printed heading · Topic match: Connecting load and generation

Because the associated special-purpose relay scheme will remove the co-located load from the grid in the event of a sudden loss of the generating facility, no energy will flow to the co-located load over the transmission grid following a contingency; no new transmission infrastructure will be…
Read this passage Filed comments: Connecting load and generation